Resolution for HWID problem with legacy EDGE E400 Controllers.

HID EDGE and EDGE EVO, Knowledge Base

Rarily, we have experienced a Hardware ID mismatch in the unit and this identity crisis does not allow you to flash the units.

To resolve the problem, utilize the setE400 (attached) utility to update the units HWID. This step may not be necessary in all instances.

  1. FTP the setE400 utility to the /tmp directory on the Edge unit.
  2. Telnet into the unit and enter chmod 775 /tmp/setE400
  3. While still in telnet, enter ./tmp/setE400. This corrects the HWID and allows you to use the FTP update method. /tmp

Investor Relations

Middleware Associates, LLC. is a privately held corporation that was founded by Patrick Conners in January, 2004. For information reqarding a potential merger, acquisition or an investment in our future technology please Contact Us